Товаров
  
корзина пуста
  • Каталог оборудования Siemens

3-phase, 36 V DC

  • Заказные данные
    (1)
  • Аксессуары
    (1)
  • Информационные материалы

    Информационные материалы

    The 3-phase SITOP modular are technology power supplies for sophisticated solutions and offer maximum functionality for use in complex plants and machines. The wide-range input allows connection to almost any electrical power system worldwide and ensures a high degree of safety, even if there are large voltage fluctuations. The power boost provides up to three times the rated current for brief periods. In case of overload, you can choose between constant current with automatic restart or latching shutdown. The high degree of efficiency keeps energy consumption and heating in the control cabinet low, and the compact metal housing also saves space.

    Main product highlights
    • 36 V DC/13 A
    • 3-phase AC input 400 to 500 volts
    • Extremely slim design – no lateral installation clearances required
    • Power Boost with 3 times the rated current (for 25 ms) for tripping protective devices
    • Extra power with 1.5 times the rated current (5 s/min) for brief functional overload
    • Choice of constant current or latching shutdown short-circuit response
    • Optional symmetrical load distribution for parallel operation
    • Operating state on 3 LEDs
    • Extremely high efficiency up to 94%
    • Wide temperature range from -25 to +70 °C
    • Comprehensive certifications, such as cULus, ATEX

    Технические данные

    Order number

    6EP3446-8SB10-0AY0

    Product

    SITOP PSU8200

    Power supply, type

    36 V/13 A

    Input

     

    Input

    3-phase AC

    Rated voltage value Vin rated

    400 ... 500 V

    Voltage range AC

    320 ... 575 V

    Wide-range input

    Yes

    Mains buffering at Iout rated, min.

    15 ms; at Vin = 400 V

    Rated line frequency 1

    50 Hz

    Rated line frequency 2

    60 Hz

    Rated line range

    47 ... 63 Hz

    Input current

     

    • at rated input voltage 400 V

    1.2 A

    • at rated input voltage 500 V

    1 A

    Switch-on current limiting (+25 °C), max.

    16 A

    I²t, max.

    0.8 A²·s

    Built-in incoming fuse

    none

    Protection in the mains power input (IEC 898)

    Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)

    Output

     

    Output

    Controlled, isolated DC voltage

    Rated voltage Vout DC

    36 V

    Total tolerance, static ±

    3 %

    Static mains compensation, approx.

    0.1 %

    Static load balancing, approx.

    0.2 %

    Residual ripple peak-peak, max.

    100 mV

    Spikes peak-peak, max. (bandwidth: 20 MHz)

    200 mV

    Adjustment range

    36 ... 42 V

    Product function Output voltage adjustable

    Yes

    Output voltage setting

    via potentiometer; max. 480 W

    Status display

    Green LED for 36 V OK

    Signaling

    Relay contact (NO contact, rating 60 V DC/ 0.3 A) for 36 V OK

    On/off behavior

    No overshoot of Vout (soft start)

    Startup delay, max.

    2.5 s

    Voltage increase time of the output voltage maximum

    500 ms

    Rated current value Iout rated

    13 A

    Current range

    0 ... 13 A

    • Note

    +60 ... +70 °C: Derating 2%/K

    Supplied active power typical

    468 W

    Short-term overload current

     

    • at short-circuit during operation typical

    39 A

    Duration of overloading capability for excess current

     

    • at short-circuit during operation

    25 ms

    Constant overload current

     

    • on short-circuiting during the start-up typical

    14 A

    Parallel switching for enhanced performance

    Yes; switchable characteristic

    Numbers of parallel switchable units for enhanced performance

    2

    Efficiency

     

    Efficiency at Vout rated, Iout rated, approx.

    94 %

    Power loss at Vout rated, Iout rated, approx.

    30 W

    Closed-loop control

     

    Dynamic mains compensation (Vin rated ±15 %), max.

    0.1 %

    Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.

    1 %

    Load step setting time 50 to 100%, typ.

    0.2 ms

    Load step setting time 100 to 50%, typ.

    0.2 ms

    Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.

    2 %

    Load step setting time 10 to 90%, typ.

    0.2 ms

    Load step setting time 90 to 10%, typ.

    0.2 ms

    Setting time maximum

    10 ms

    Protection and monitoring

     

    Output overvoltage protection

    < 48 V

    Current limitation, typ.

    14 A

    Property of the output Short-circuit proof

    Yes

    Short-circuit protection

    Alternatively, constant current characteristic approx. 14 A or latching shutdown

    Enduring short circuit current RMS value

     

    • typical

    14 A

    Overcurrent overload capability in normal operation

    overload capability 150 % Iout rated up to 5 s/min

    Overload/short-circuit indicator

    LED yellow for "overload", LED red for "latching shutdown"

    Safety

     

    Primary/secondary isolation

    Yes

    Galvanic isolation

    Safety extra low output voltage Vout according to EN 60950-1

    Protection class

    Class I

    Leakage current

     

    • maximum

    3.5 mA

    • typical

    0.9 mA

    CE mark

    Yes

    UL/cUL (CSA) approval

    cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259

    Explosion protection

    No

    FM approval

    -

    CB approval

    Yes

    Marine approval

    GL, ABS

    Degree of protection (EN 60529)

    IP20

    EMC

     

    Emitted interference

    EN 55022 Class B

    Supply harmonics limitation

    EN 61000-3-2

    Noise immunity

    EN 61000-6-2

    Operating data

     

    Ambient temperature

     

    • during operation

    -25 ... +70 °C

    • Note

    with natural convection

    • during transport

    -40 ... +85 °C

    • during storage

    -40 ... +85 °C

    Humidity class according to EN 60721

    Climate class 3K3, no condensation

    Mechanics

     

    Connection technology

    screw-type terminals

    Connections

     

    • Supply input

    L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded

    • Output

    +, -: 2 screw terminals each for 0.2 ... 4 mm²

    • Auxiliary

    13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²; 15, 16 (Remote): 1 screw terminal each for 0.14 ... 1.5 mm²

    Width of the enclosure

    70 mm

    Height of the enclosure

    125 mm

    Depth of the enclosure

    125 mm

    Required spacing

     

    • top

    50 mm

    • bottom

    50 mm

    • left

    0 mm

    • right

    0 mm

    Weight, approx.

    1.2 kg

    Product feature of the enclosure housing for side-by-side mounting

    Yes

    Installation

    Snaps onto DIN rail EN 60715 35x7.5/15

    Electrical accessories

    Buffer module

    Mechanical accessories

    Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20

    Other information

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)


    Дополнительно

    Device labeling plates

    3RT1900-1SB20