Товаров
  
корзина пуста
  • Каталог оборудования Siemens

1-phase, 24 V DC

  • Заказные данные
    (5)
  • Аксессуары
    (10)
  • Информационные материалы

    Информационные материалы

    The 1-phase SITOP modular are technology power supplies for sophisticated solutions and offer maximum functionality for use in complex plants and machines. The wide-range input allows a connection to almost any electrical power system worldwide and ensures a high degree of safety even if there are large voltage fluctuations. The power boost provides up to three times the rated current for brief periods. In case of overload, you can choose between constant current with automatic restart or latching shutdown. The high degree of efficiency keeps energy consumption and heating in the control cabinet low, and the compact metal housing also saves space.

    To further increase the 24 V availability, the SITOP modular power supplies can be combined with buffer, DC UPS, redundancy and selectivity modules.

    Main product highlights
    • 24 V DC/ 5 A, 10 A, 20 A and 40 A
    • 1-phase wide-range input for connection to any supply system and for safety in case of voltage supply deviations
    • Extremely slim design – no lateral installation clearances required
    • Power Boost with 3 times the rated current (for 25 ms) for tripping protective devices
    • Extra power with 1.5 times the rated current (5 s/min) for brief functional overload
    • Selectable short-circuit response between constant current and restart
    • Optional symmetrical load distribution for parallel operation
    • Operating status on 3 LEDs
    • Extremely high efficiency to 94 %
    • Wide temperature range from -25 to +70 °C
    • Comprehensive certifications, such as cULus, ATEX and GL

    Технические данные

    Order number

    6EP3333-8SB00-0AY0

    6EP3334-8SB00-0AY0

    6EP1336-3BA10

    6EP3337-8SB00-0AY0

    Product

    SITOP PSU8200

    SITOP PSU8200

    SITOP PSU8200

    SITOP PSU8200

    Power supply, type

    24 V/5 A

    24 V/10 A

    24 V/20 A

    24 V/40 A

    Input

     

     

     

     

    Input

    1-phase AC

    1-phase AC

    1-phase AC or DC

    1-phase AC

    Supply voltage

     

     

     

     

    • 1 at AC Rated value

    120 V

    120 V

    120 V

    • 2 at AC Rated value

    230 V

    230 V

    230 V

    • at DC

    110 ... 220 V

    Rated voltage value Vin rated

    120 ... 230 V

    Voltage range AC

    85 ... 275 V

    • Note

    Automatic range selection

    Automatic range selection

    Derating of temperature necessary down to 50 °C at Vin < 100 V AC or DC

    Automatic selection; startup starting from Ue ≥ 90/180 V

    Input voltage

     

     

     

     

    • 1 at AC

    85 ... 132 V

    85 ... 132 V

    85 ... 132 V

    • 2 at AC

    170 ... 264 V

    170 ... 264 V

    170 ... 264 V

    • at DC

    88 ... 350 V

    Wide-range input

    No

    No

    Yes

    No

    Mains buffering at Iout rated, min.

    35 ms; at Vin = 120/230 V

    35 ms; at Vin = 120/230 V

    20 ms; at Vin = 230 V

    25 ms; at Vin = 230 V

    Rated line frequency 1

    50 Hz

    50 Hz

    50 Hz

    50 Hz

    Rated line frequency 2

    60 Hz

    60 Hz

    60 Hz

    60 Hz

    Rated line range

    47 ... 63 Hz

    47 ... 63 Hz

    45 ... 65 Hz

    45 ... 65 Hz

    Input current

     

     

     

     

    • at rated input voltage 120 V

    2.1 A

    4 A

    4.6 A

    15 A

    • at rated input voltage 230 V

    1.2 A

    1.9 A

    2.5 A

    9 A

    Switch-on current limiting (+25 °C), max.

    10 A

    10 A

    20 A

    60 A

    I²t, max.

    0.2 A²·s

    0.3 A²·s

    5 A²·s

    8 A²·s

    Built-in incoming fuse

    T 3.15 A (not accessible)

    T 6.3 A (not accessible)

    Yes

    Yes

    Protection in the mains power input (IEC 898)

    Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V

    Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V

    Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V

    Recommended miniature circuit breaker at 1-phase operation: 16 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2421-4BA10 (120 V) or 3RV2411-1JA10 (230 V)

    Output

     

     

     

     

    Output

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Rated voltage Vout DC

    24 V

    24 V

    24 V

    24 V

    Total tolerance, static ±

    3 %

    3 %

    3 %

    3 %

    Static mains compensation, approx.

    0.1 %

    0.1 %

    0.1 %

    0.1 %

    Static load balancing, approx.

    0.2 %

    0.3 %

    0.3 %

    0.1 %

    Residual ripple peak-peak, max.

    50 mV

    50 mV

    100 mV

    100 mV

    Residual ripple peak-peak, typ.

    80 mV

    50 mV

    Spikes peak-peak, max. (bandwidth: 20 MHz)

    200 mV

    200 mV

    200 mV

    240 mV

    Spikes peak-peak, typ. (bandwidth: 20 MHz)

    100 mV

    220 mV

    Adjustment range

    24 ... 28.8 V

    24 ... 28.8 V

    24 ... 28.8 V

    24 ... 28 V

    Product function Output voltage adjustable

    Yes

    Yes

    Yes

    Yes

    Output voltage setting

    via potentiometer; max. 120 W

    via potentiometer; max. 240 W

    via potentiometer

    via potentiometer; max. 960 W

    Status display

    Green LED for 24 V OK

    Green LED for 24 V OK

    Green LED for 24 V OK

    Green LED for 24 V OK; LED yellow for overload; LED red for short-circuit or latching shutdown

    Signaling

    Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"

    Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"

    Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"

    Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"

    On/off behavior

    Overshoot of Vout approx. 3 %

    Overshoot of Vout approx. 3 %

    No overshoot of Vout (soft start)

    Overshoot of Vout approx. 3 %

    Startup delay, max.

    1 s

    1 s

    0.25 s

    1.5 s

    Voltage rise, typ.

    30 ms

    70 ms

    50 ms

    30 ms

    Rated current value Iout rated

    5 A

    10 A

    20 A

    40 A

    Current range

    0 ... 5 A

    0 ... 10 A

    0 ... 20 A

    0 ... 40 A

    • Note

    As of Ua>24 V: 4% [Ia]/V [Ua]; at Ue<100 V/<200 V: 80% Ia rated

    +60 ... +70 °C: Derating 2%/K; as of Ua>24 V: 4% [Ia]/V [Ua]; at Ue<100 V/<200 V: 80% Ia rated

    +60 ... +70 °C: Derating 3%/K

    +60 ... +70 °C: Derating 3%/K

    Supplied active power typical

    120 W

    240 W

    480 W

    960 W

    Short-term overload current

     

     

     

     

    • on short-circuiting during the start-up typical

    120 A

    • at short-circuit during operation typical

    15 A

    30 A

    60 A

    120 A

    Duration of overloading capability for excess current

     

     

     

     

    • on short-circuiting during the start-up

    25 ms

    • at short-circuit during operation

    25 ms

    25 ms

    25 ms

    25 ms

    Constant overload current

     

     

     

     

    • on short-circuiting during the start-up typical

    6 A

    12 A

    30 A

    60 A

    Parallel switching for enhanced performance

    Yes; switchable characteristic

    Yes; switchable characteristic

    Yes; switchable characteristic

    Yes; switchable characteristic

    Numbers of parallel switchable units for enhanced performance

    2

    2

    2

    2

    Efficiency

     

     

     

     

    Efficiency at Vout rated, Iout rated, approx.

    93 %

    94 %

    93 %

    92 %

    Power loss at Vout rated, Iout rated, approx.

    9 W

    18 W

    42 W

    82 W

    Power loss [W] during no-load operation maximum

    1.5 W

    1.5 W

    6.8 W

    Closed-loop control

     

     

     

     

    Dynamic mains compensation (Vin rated ±15 %), max.

    0.1 %

    0.1 %

    0.5 %

    1 %

    Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.

    2 %

    4 %

    1 %

    1.9 %

    Load step setting time 50 to 100%, typ.

    0.25 ms

    0.25 ms

    1 ms

    2 ms

    Load step setting time 100 to 50%, typ.

    0.5 ms

    0.5 ms

    1 ms

    2 ms

    Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.

    2 %

    4 %

    3.8 %

    Load step setting time 10 to 90%, typ.

    0.25 ms

    0.25 ms

    1 ms

    Load step setting time 90 to 10%, typ.

    0.5 ms

    0.5 ms

    1 ms

    Setting time maximum

    1 ms

    1 ms

    5 ms

    1 ms

    Protection and monitoring

     

     

     

     

    Output overvoltage protection

    < 33 V

    < 33 V

    < 33 V

    < 32 V

    Current limitation, typ.

    6 A

    12 A

    21.5 A

    41 A

    Property of the output Short-circuit proof

    Yes

    Yes

    Yes

    Yes

    Short-circuit protection

    Alternatively, constant current characteristic approx. 6 A or latching shutdown

    Alternatively, constant current characteristic approx. 12 A or latching shutdown

    Alternatively, constant current characteristic approx. 23 A or latching shutdown

    Alternatively, constant current characteristic approx. 41 A or latching shutdown

    Enduring short circuit current RMS value

     

     

     

     

    • typical

    6 A

    12 A

    23 A

    41 A

    Overcurrent overload capability in normal operation

    overload capability 150 % Iout rated up to 5 s/min

    overload capability 150 % Iout rated up to 5 s/min

    overload capability 150 % Iout rated up to 5 s/min

    250% Iout rated up to 25 ms, 150% Iout rated up to 5 s/min

    Overload/short-circuit indicator

    LED yellow for "overload", LED red for "latching shutdown"

    LED yellow for "overload", LED red for "latching shutdown"

    LED yellow for "overload", LED red for "latching shutdown"

    LED yellow for "overload", LED red for "latching shutdown" or "short-circuit"

    Safety

     

     

     

     

    Primary/secondary isolation

    Yes

    Yes

    Yes

    Yes

    Galvanic isolation

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Protection class

    Class I

    Class I

    Class I

    Class I

    Leakage current

     

     

     

     

    • maximum

    3.5 mA

    3.5 mA

    3.5 mA

    0.1 mA

    • typical

    1 mA

    1 mA

    1 mA

    0.1 mA

    CE mark

    Yes

    Yes

    Yes

    Yes

    UL/cUL (CSA) approval

    cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, cCSAus (CSA C22.2 No. 60950-1, UL 60950-1, UL 1604)

    cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, cCSAus (CSA C22.2 No. 60950-1, UL 60950-1, UL 1604)

    cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259

    cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

    Explosion protection

    IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3

    IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3

    IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3

    IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3; cULus (Hazloc) Class I, Div. 2, Group ABCD, T3; File E330455

    FM approval

    -

    -

    -

    -

    CB approval

    Yes

    Yes

    No

    Yes

    Marine approval

    GL, ABS

    GL, ABS

    GL, ABS

    GL; ABS in process

    Degree of protection (EN 60529)

    IP20

    IP20

    IP20

    IP20

    EMC

     

     

     

     

    Emitted interference

    EN 55022 Class B

    EN 55022 Class B

    EN 55022 Class B

    EN 55022 Class B

    Supply harmonics limitation

    EN 61000-3-2

    EN 61000-3-2

    EN 61000-3-2

    -

    Noise immunity

    EN 61000-6-2

    EN 61000-6-2

    EN 61000-6-2

    EN 61000-6-2

    Operating data

     

     

     

     

    Ambient temperature

     

     

     

     

    • during operation

    -25 ... +70 °C

    -25 ... +70 °C

    -25 ... +70 °C

    -25 ... +70 °C

    • Note

    With natural convection; startup tested starting from -40 °C nominal voltage

    With natural convection; startup tested starting from -40 °C nominal voltage

    With natural convection; startup tested starting from -40 °C nominal voltage

    with natural convection

    • during transport

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    • during storage

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    Humidity class according to EN 60721

    Climate class 3K3, no condensation

    Climate class 3K3, no condensation

    Climate class 3K3, no condensation

    Climate class 3K3, no condensation

    Mechanics

     

     

     

     

    Connection technology

    screw-type terminals

    screw-type terminals

    screw-type terminals

    screw-type terminals

    Connections

     

     

     

     

    • Supply input

    L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely stranded

    L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely stranded

    L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded

    L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded

    • Output

    +, -: 2 screw terminals each for 0.2 ... 2.5 mm²

    +, -: 2 screw terminals each for 0.2 ... 2.5 mm²

    +, -: 2 screw terminals each for 0.2 ... 4 mm²

    +, -: 2 screw terminals each for 0.5 ... 10 mm²

    • Auxiliary

    13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²; 15, 16 (Remote): 1 screw terminal each for 0.14 ... 1.5 mm²

    13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²; 15, 16 (Remote): 1 screw terminal each for 0.14 ... 1.5 mm²

    13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²

    13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²

    Width of the enclosure

    45 mm

    55 mm

    90 mm

    145 mm

    Height of the enclosure

    125 mm

    125 mm

    125 mm

    145 mm

    Depth of the enclosure

    125 mm

    125 mm

    125 mm

    150 mm

    Required spacing

     

     

     

     

    • top

    50 mm

    50 mm

    50 mm

    40 mm

    • bottom

    50 mm

    50 mm

    50 mm

    40 mm

    • left

    0 mm

    0 mm

    0 mm

    0 mm

    • right

    0 mm

    0 mm

    0 mm

    0 mm

    Weight, approx.

    0.8 kg

    1 kg

    1.2 kg

    3.1 kg

    Product feature of the enclosure housing for side-by-side mounting

    Yes

    Yes

    Yes

    Yes

    Installation

    Snaps onto DIN rail EN 60715 35x7.5/15

    Snaps onto DIN rail EN 60715 35x7.5/15

    Snaps onto DIN rail EN 60715 35x7.5/15

    Snaps onto DIN rail EN 60715 35x15

    Electrical accessories

    Buffer module

    Buffer module

    Buffer module

    Buffer module, redundancy module

    Mechanical accessories

    Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20

    Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20

    MTBF at 40 °C

    1 421 519 h

    1 292 102 h

    667 048 h

    838 156 h

    Other information

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)


    Дополнительно

    SITOP PSE201U buffer module

    6EP1961-3BA01

    For SITOP smart and SITOP modular
    buffer time 100 ms to 10 s
    dependent on load current 

     

    SITOP modular signaling module

    6EP1961-3BA10

    For 6EP1XXX-3BA00
    signaling contacts: Output voltage OK
    , readiness for operation OK, remote ON/OFF

     

    SITOP PSE202U redundancy module

    6EP1961-3BA21

    Input/output: 24 V DC/40 A
    suitable for decoupling two SITOP power supplies with a maximum of 20 A output current

     

    SITOP PSE202U redundancy module

    6EP1962-2BA00

    Input/output: 24 V DC/NEC Class 2
    suitable for decoupling two SITOP power supplies;
    output power limited < 100 VA

     

    SITOP PSE202U redundancy module

    6EP1964-2BA00

    Input/output: 24 V DC/10 A
    suitable for decoupling two SITOP power supplies with a maximum of 5 A output current

     

    SITOP PSE200U selectivity module 3 A

     

    4-channel
    Input: 24 V DC
    Output: 24 V DC/3 A per channel
    Adjustable output current 0.5 … 3 A

     
    • With common alarm signal

    6EP1961-2BA11

    • With single-channel signaling

    6EP1961-2BA31

    SITOP PSE200U selectivity module 10 A

     

    4-channel
    Input: 24 V DC
    Output: 24 V DC/10 A per channel
    Adjustable output current 3 ... 10 A

     
    • With common alarm signal

    6EP1961-2BA21

    • With single-channel signaling

    6EP1961-2BA41

    Device labeling plates

    3RT1900-1SB20